VoltageWardenSixth Day Studios AS/NZS 3008.1.1 · copper

Circuit

Supply
Load
Cable

Distances to check

Leave blank to check around your run length.

Advanced: derating and limits

AS/NZS 3008 ratings assume 40 °C air, 25 °C soil and 0.5 m burial depth. Count this circuit in the number grouped.

AS/NZS 3000 allows 5% from the point of supply to the load, so count the drop on the mains and sub-mains too.

Earth fault loop

Breakers use the AS/NZS 3000 Table 8.1 trip currents (B 4×, C 7.5×, D 12.5× rating). For a fuse, enter the current that blows it in 0.4 s (final subcircuits to 63 A with sockets or hand-held gear) or 5 s, from its curve. With no Zext, Appendix B's method assumes 80% of the voltage is left at the origin.

Over distance

Every size

Tap a row to use that size

Cables in conduit

Conduit
Cables in each conduit

Diameters are typical catalogue figures. Pick "Other" to type one from the datasheet.

Underground run

For parallel cables, one parallel set per conduit is usual: set this to the number of sets.

Every conduit size

Tap a row to use that size