Advanced: derating and limits
AS/NZS 3008 ratings assume 40 °C air, 25 °C soil and 0.5 m burial depth. Count this circuit in the number grouped.
AS/NZS 3000 allows 5% from the point of supply to the load, so count the drop on the mains and sub-mains too.
Earth fault loop
Breakers use the AS/NZS 3000 Table 8.1 trip currents (B 4×, C 7.5×, D 12.5× rating). For a fuse, enter the current that blows it in 0.4 s (final subcircuits to 63 A with sockets or hand-held gear) or 5 s, from its curve. With no Zext, Appendix B's method assumes 80% of the voltage is left at the origin.