Voltage drop and cable current rating in one go. Enter the voltage, load, run length, cable and how it's installed, and see straight away whether the cable works and what size you need.

Free with no account and nothing to install
  • It opens in your browser on a phone, tablet or PC. Add to Home Screen (phone) or Install app (Edge or Chrome) gives it its own icon.
  • It works with no signal once you've opened it, in the switchroom or down the pit.
  • Nothing leaves your device, and your last circuit is remembered on that device only.
VoltageWarden showing a 2.5 mm² cable, its rating and voltage drop over 30 metres.
Cable size, voltage drop and longest run for a circuit.
VoltageWarden conduit planner showing fill for every conduit size.
Cables in conduit, with the fill for every size.

What it checks

  • It works out voltage drop by the AS/NZS 3008.1.1 method, in volts and percent, against the 5% AS/NZS 3000 limit (or your own).
  • It checks current carrying capacity for how the cable is run, whether in conduit, clipped to a surface, on tray or ladder, in thermal insulation, in underground conduit or buried direct.
  • It finds the smallest size that works, or says why your chosen size doesn't, plus a table of every size with its rating, drop and longest run.
  • Over distance, it shows the drop at the run lengths you list, and the longest run that stays within the limit.
  • The load can be in amps or kW. Pick a load type (heating, lighting, motor, air conditioning, EV charger) and it sets the power factor for you.
  • Advanced options, for when you need them, cover air or soil temperature, grouping with other circuits, burial depth, and a circuit breaker check (load ≤ breaker ≤ cable rating).

Cables

  • TPS flat 2C+E and 3C+E
  • SDI single core (V-90)
  • XLPE single core and XLPE multicore (X-90)
  • Orange circular 4-core and 5-core (V-90)

Copper conductors, single-phase and three-phase, 1 mm² to 630 mm² depending on the cable.

Accuracy and privacy

  • It's checked against AS/NZS 3008.1.1:2017. Voltage drop matches the standard's tables to within 1%. Current ratings come from a model calibrated against the standard's tables. On average they sit about 2.5% below the tables, and never more than 2% above. It's a design aid, so check the final selection against the standard and the cable maker's data.
  • Voltage drop is worst case, with the cable at its maximum operating temperature, as the standard's own tables assume.
  • The privacy policy has the details.

If VoltageWarden saved you time, you can chip in to keep it going. You don't have to, and it works the same either way.